Talking about the Design and Application of Fire-fighting Equipment Power Monitoring System

Xu Shuang

Ankerui Electric Co., Ltd., Shanghai Jiading 201801

0 Preface

(1) Miscellaneous firefighting facilities

A large number of fire-fighting products have been set up in modern large-scale buildings, public gathering places and high-rise buildings: automatic repertoire systems, automatic sprinkler systems, fire-fighting broadcasting, telephones, smoke control systems, electrical fire monitoring systems, gas fire extinguishing Systems, fire extinguishing systems, emergency lighting systems, fire elevators, shutter doors, etc.

(2) Potential for power out of control

Fire safety depends largely on the quality of fire fighting equipment. The proper operation of the fire fighting system and related fire fighting linkage equipment depends on the working status of its power supply.

All along, failure of fire control equipment caused by the loss of control of equipment power has resulted in frequent fire incidents, especially during periods of intense social power supply, poor equipment quality, and weak safety awareness. This problem is even more prominent.

Mainly suitable for some large public buildings, densely populated places:

1) Large-scale disease hospitals (ward building, out-patient building), theaters, halls, auditoriums, gyms, department stores, and shopping malls;

2) Exhibition buildings, high-class hotels, financial and financial buildings, telecommunication buildings, and high-grade office buildings;

3) Civil buildings such as underground railways, railway stations, tunnels, bus stations, cinemas, and auditoriums.

1 system structure

The AFPM100 fire-fighting equipment power monitoring system adopts a three-layer structure networking mode of the power equipment + monitoring module + system host, thereby simplifying the system structure design. The entire monitoring system is full-featured, safe and reliable, with accurate detection and high cost performance. The system uses RS485 network communication internally and provides Modbus-RTU communication protocol externally to meet the connection of other standard systems.

2 system function

(1) Monitoring alarm

(2) Fault alarm

(3) Control output

(4) Self test

(5) Alarm record

(6) Operation classification

3 Design Cases

3.1 System Wiring Diagram

(1) Network topology of small and medium-sized monitoring systems

Module AFPM-â–¡ is a sensor (monitoring module). The monitor (host) can receive and display the operating status of the monitored fire-fighting equipment power supply and the relay's working status.
When the transmission distance is greater than 500m, a repeater is added. The 1-in. repeater occupies 1 sensor (monitoring module) address. The repeater's AC220V power cable is 3*1.5mm^2. It consists of on-site fire power or fire control room. Monitor (host) provided.
The transmission mode is RS485 bus, which is represented by A/B in the figure. The cable shielding layer should be reliably connected with the protection ground of the monitor (host).
Each type of sensor (monitoring module) sets the communication address with the monitor (host) via a code switch.
According to the engineering needs, a 120Ω-10KΩ/1W matching resistor should be connected at the most remote sensor (monitoring module) on the communication line to improve the communication stability.
The general power monitor (host) has 4 output circuits and each circuit can connect 32 sensors (monitoring modules). Special loops can be extended in special cases.

(2) Large-scale monitoring system network topology

This system is used when there are many buildings or field facilities and needs to be divided into multiple areas.
Each zone monitor (host) can collect 128 sensors (monitoring modules), which can be expanded in special cases.
The main power supply for the monitor (mainframe) is AC220V. The standby power supply can be provided on site or on site.

3.2 Design Considerations

(1) Description of power supply and communication cable

1 The communication line between the monitoring host and the detector adopts the bus type (hand-in-hand) connection mode;

2 The diameter of the communication line between the host computer and the module should not be less than 2x1.0mm cable;

3 detector power line is not less than 2x 1.5mm.

(2) Installation location

1) Monitoring host

1 monitoring host installed in the fire control room;

2 It is dedicated to the power supply monitoring of fire-fighting equipment and installed independently. It cannot use the monitoring of other functions, and does not share the equipment with other systems to ensure the stability and safety of the system;

3 host dedicated power supply AC220V provided by the fire power.

2) Detector

Installed in a special cabinet (box) near the power supply for the fire-fighting equipment on the monitored side. under special condition. Can be installed in the power distribution box of the monitored fire protection equipment power supply.

(3) Configuration of the detector

1) The setting of the detector should be set at the end; the power of the fire-fighting equipment monitored by the detector should include the fire-fighting facilities in the following table;

2) The system's voltage sensor and current sensor should be set so that the power supply status of the entire fire protection system can be displayed on the monitor or in the fire control room in real time. It should be set in the following locations; the output terminal of the power distribution cabinet for the main power supply and fire power supply for the fire protection equipment within the building; the dual power input and output terminal for the fire protection electrical control device (including the water pump controller, fan controller, etc.) The output terminals of the fire-fighting equipment power supply devices (DC power supplies for each fire-fighting equipment) installed in each fire prevention zone; the output terminals of the power distribution box for fire-fighting equipment; the eager end and output end of emergency power supply for fire-fighting equipment; emergency The output terminal of the lighting distribution box; the input and output terminals of the emergency power supply for the centralized power type fire emergency luminaires; the equipment of the multiple main power supply should monitor the input terminals of each main power supply circuit.

3) The operating status of the following fire-fighting equipment independently provided by the fire control room is not shown on the fire alarm controller or fire-fighting linkage controller. A voltage sensor or a current sensor should be installed at the output of the power supply. .

Electrical fire monitoring equipment; Combustible gas controllers; Fire shutter controllers; Gas fire control controllers; Linear fiber-optic heat detectors; Air sampling smoke detection detectors; Transmission equipment; Fire display panels; Other fire protection equipment.

4 Equipment List

No.

name

Model, specification

unit

Note

1

Power Meter

AFPM power monitoring module

AFPM3-2AV

station

Ankerui

AFPM power monitoring module

AFPM1-AV

station

Ankerui

total

2

Monitoring Center duty room

Fire power monitoring equipment

Acrel-AFPM wall-mounted

set

Ankerui

Fire power monitoring equipment main components

display board

AFPM100

Piece

Ankerui

Control board

AFPM100-P

Piece

Ankerui

Panasonic UPS battery

12V24Ah(165*125*175)

Section

Matsushita

Thermal printer

RD-E32-485-24V (with Chinese font library)

station

Switching power supply

TPC-H180SBAT

only

Auxiliary materials

set

total

3

Engineering Materials

Communication cable

ZR-RVSP 2*1.0

km

power cable

ZR-RVV 3*1.5

Meter

Engineering materials

Towboards, conversion lines, lines, signs, etc.

set

total

4

Construction and commissioning

Communication cable laying

Meter

Instrument communication line connection

only

Instrument communication debugging

only

Comprehensive debugging

People/day

Equipment transportation costs

item

training fees

item

5 Concluding remarks

Implement the two national standards of "General Technical Requirements for Fire Control Room" and "Fire Control System for Power Supply", promote the application of "Fire Equipment Power Supply Monitoring System", comply with "The Opinions of the State Council on Strengthening and Improving Fire Protection Work," and "The Fire Department". Promote the development of more stringent fire safety standards in big cities." Implement the spirit of stricter fire safety standards. Not only provides a technical basis for the actual use of the fire protection department's law enforcement supervision and design and construction units, but also takes the lead in realizing a positive effect of effectively reducing the incidence of fire fighting equipment, building fire hazards, and protecting people’s lives and national property safety. The system realizes effective real-time monitoring in the fire control room, and displays various technical requirements for the working status of the power supply and standby power supply of each fire-fighting electrical equipment, and is applicable to new, expanded and rebuilt industrial and civil buildings. The system plays an important role in ensuring that the construction fire-fighting facilities are in good condition, improving the fire-fighting safety management level of all units, detecting the failure of fire-fighting equipment in a timely manner, and preventing and reducing fire hazards.

references:

[1]The application of fire-fighting equipment power monitoring system in the field. Wang Lei, Yao Shaojun. Electrical & Intelligent Buildings, 2013.11

[2] Ankerui Electric Co., Ltd. Product Selection Manual 2013.1.

[3] Zhou Zhongzhong, ed. Smart grid customer end power monitoring and power management system product selection and solution IV. Beijing Machinery Industry Press, 2011.10

About the Author:

Xu Shuang, female, undergraduate, Ankerui Electric Co., Ltd., the main research direction for the design of electrical fire monitoring and fire protection equipment power monitoring, mobile phone QQ

"Atlas of Design and Application of Fire-fighting Equipment Power Monitoring System" (atlas number: ACR13CDX801) is edited by Ankerui Electric Co., Ltd. This atlas combines the characteristics of the AFPM series fire-fighting equipment power monitoring system and meets the requirements of electrical design specifications. The object monitors the normal use requirements of the fire-fighting equipment power supply so as to prevent the fire-fighting equipment from working normally when a fire occurs. The Atlas was compiled by the Honorary Chairman of the Electrical Engineering Committee of the Yunnan Civil Engineering Society, the Director of the Yunnan Provincial Architectural Design Institute Deng Zhao, the Vice Chairman and Secretary-General of the Hunan Electric Design Information Network, and the Chief Engineer of Hunan Provincial Architectural Design Institute. Liang Zhichao's review. The Atlas is applicable to the design and application of fire protection equipment power supply monitoring systems for 220V/380V power supply and distribution systems in new, expanded and rebuilt industrial and civil buildings and general industrial buildings, and includes the selection and installation of system equipment. Buildings with special requirements must be selected in combination with the actual conditions of the project. If you need an atlas, please provide your organization's name, department, address, zip code, contact person, contact telephone number, email address, fax, email@qq.com or QQ to Ankeru Xu cream engineer, Ankerui Electric Give away.

Monitored equipment power circuit switch status Monitored equipment power supply working status (voltage, current and alarm status information) Alarm response time: ≤ 30s Alarm sound signal: Can be manually eliminated, when the alarm signal is input again, the alarm light can be activated again Signals: Red LED light is always on. Connection between monitor and module (voltage/current signal sensor) Line break, short circuit monitor Mains undervoltage (≤80% mains voltage) or overvoltage (≥110% mains Voltage) Disconnection and short circuit between the monitor and its split power supply. When the monitor has the above fault, it can send a sound and light fault alarm signal with obvious difference from the monitoring alarm signal. Fault alarm response time: ≤100s Fault alarm sound signal: Manual Eliminating, when there is alarm signal input again, the fault alarm light signal can be activated again: Yellow LED indicator is on during the fault, the normal operation of the non-fault circuit is not affected Remote control of alarm relays of some or all monitored devices Monitor alarm control output: normally open passive contact, capacity: AC250V 3A or DC30V 3A monitor Controller control output: Normally open passive contact, Capacity: AC250V 3A or DC30V 3A Connection check: Disconnection and short circuit of communication line and split power supply line Device self-check: manual check or system self-check self-check Time-consuming: ≤60s Record 1000 related fault alarm information Types of alarm: Fault type, occurrence time, fault description Alarm event query Alarm record printing Daily duty class: Can enter software interface to view real-time monitoring situation, eliminate alarm sound and query alarm record monitoring Operation level: Operational Except for the maintenance of information on the system itself, other operating system management levels: any functional module of the operating system

CO2 Laser Cutting Engraving Machine Series--Nonmetal materials

Applicable Materials:
wood, bamboo, jade, marble, organic glass, double-color sheets, crystal, plastic, garments, paper, leather, rubber, ceramic, glass, film, cut and other nonmetal materials.
Note: with Oxygen, the machine can cut thin metal sheet such as steel.

Applicable Industries:
sticker cutting and engraving .Marble engraving industry ,advertisement, gift packing,

shoes, garments, toys, model, decoration, arts and crafts, paper industry, etc.


laser engraving machine for rubber

6040 smaller laser engraving machine

granite stone laser engraving machine

CO2 laser cutter machine for sale

cnc laser machine engraver router

wood laser cutting machine

laser machine for mdf cutting

smaller  desktop MDF laser cutting  engraving machine



PVC cutting laser

plywood laser cutting machine


RFQ

Q1: How can I get the best machine for me?
You can tell us your working material, detail work by picture or video so that we can judge whether our machine can meet your need or not. Then we can give you the best model depends on our experience.

Q2: What`s the package?
We have 3 layers package. For the outside, we adopt wood craft case. In the middle, the machine is covered by foam, to protect the machine from shaking. For the inside layer, the machine is covered by thickening plastic bag for waterproof.

Q3: How to install and run the machine?
A: Our technician have installed the machine before shipping. For some small parts installation, we will send detail training video, user's manual along with the machine. 95% customers can learn by themselves.

Q4: How can I do if the machine goes wrong?
A: If confronted with such problems, please contact us asap and do not try fix the machine by yourself or someone else. We will response within 24 hours as quick as we can to solve it for you.

Laser Machine Series

Laser Machine,Laser Engraving Machine,Laser Engraver,Laser Cutter

Shandong U-May CNC Technology Co., Ltd. , http://www.fiberlasers.de

This entry was posted in on